• We are now running on a new, and hopefully much-improved, server. In addition we are also on new forum software. Any move entails a lot of technical details and I suspect we will encounter a few issues as the new server goes live. Please be patient with us. It will be worth it! :) Please help by posting all issues here.
  • The forum will be down for about an hour this weekend for maintenance. I apologize for the inconvenience.
  • If you are having trouble seeing the forum then you may need to clear your browser's DNS cache. Click here for instructions on how to do that
  • Please review the Forum Rules frequently as we are constantly trying to improve the forum for our members and visitors.

Has Virginia adoped the NFPA code regarding powder and primers?

hsmith

Regular Member
Joined
Mar 29, 2007
Messages
1,687
Location
Virginia USA, ,
imported post

Below:

Small Arms Ammunition and Primers, Smokeless Propellants, and Black Powder Propellants

11-1 Basic Requirements.

11-1.1 In addition to all other applicable requirements of this code, intrastate transportation of small arms ammunition, small arms primers, smokeless propellants, and black powder shall comply with US Department of Transportation Hazardous Materials Regulations, 49 CFR, Parts 100-199.

11-1.2 This chapter applies to the channels of distribution of and to the users of small arms ammunition, small arms primers, smokeless propellants, and black powder.

11-1.3 This chapter does not apply to in-process storage and intra-plant transportation during manufacture.

11-1.4 This chapter applies to the transportation and storage of small arms ammunition and components.

11-1.5 This chapter does not apply to safety procedures in the use of small arms ammunition and components.

11-5 Small Arms Primers

11-5.1 Small arms primers shall be transported or stored in containers approved by the US Department of Transportation.

11-5.2 Transportation of small arms primers shall comply with US Department of Transportation Regulations.

11-5.3 No more than 25,000 small arms primers may be transported in a private vehicle.

11-5.4 No more than 10,000 small arms primers may be stored in residences.

11-5.5 No more than 10,000 small arms primers may be displayed in commercial establishments.

11-5.6 Commercial stocks of small arms primers shall be stored as follows:

(a) Quantities not exceeding 750,000 may be stored in a building if not more than 100,000 are stored in any one pile and piles are at least 15 ft (4.6 m) apart.

(b) Quantities exceeding 750,000 may be stored in a building if the following conditions are met:

1. The warehouse or storage room shall not be accessible to unauthorized personnel.

2. Primers shall be stored in cabinets. No more than 200,000 primers shall be stored in any one cabinet.

3. Shelves in cabinets shall have vertical separation of at least 2 ft (0.6 m).

4. Cabinets shall be located against walls of the warehouse or storage room with at least 40 ft (12.2 m) between cabinets.

5. Separation between cabinets may be reduced to 20 ft (6.1 m) if barricades twice the height of the cabinets are attached to the wall, midway between each cabinet. The barricades shall extend at least 10 ft (3 m) outward, shall be firmly attached to the wall, and shall be constructed of 1/4 in. (6.4 mm) boiler plate, 2 in. (51 mm) thick wood, brick or concrete block.

6. Primers shall be separated from materials classified by the US Department of Transportation as flammable liquids, flammable solids, and oxidizing materials by a distance of 25 ft (7.63 m) or by a fire partition having a fire resistance of at least 1 hour.

Reprinted with permission from NFPA 495: Explosive Material Code, Copyright ©1992, National Fire Protection Association, Quincy , MA 02269 . This reprinted material is not the complete and official position of the National Fire Protection Association on the referenced subject which is represented only by the standard in its entirety.

13-3 SMOKELESS PROPELLANTS

13-3.1 Quantities of smokeless propellants not exceeding 25 lb (11.3 kg), in shipping containers approved by the U.S. Department of Transportation, shall be permitted to be transported in a private vehicle.

13-3.2 Quantities of smokeless propellants exceeding 25 lb (11.3 kg) but not exceeding 50 lb (22.7 kg), transported in a private vehicle, shall be transported in a portable magazine having wood walls of at least 1 in. (25.4 mm) nominal thickness.

13-3.3 Transportation of more than 50 lb (22.7 kg) of smokeless propellants in a private vehicle shall be prohibited.

13-3.4 Commercial shipments of smokeless powder for small arms which has been classed in Division 1.3 shall be permitted to be reclassed as Division 4.1 Flammable Solid for transportation purposes for shipment by motor vehicle, rail car, vessel, or cargo-only aircraft, subject to the conditions stated in the U.S. Department of Transportation "Hazardous Materials Regulations," 49 CFR 173.171.

13-3.5 Commercial shipments of smokeless propellants exceeding 100 lb (45.4 kg) or not packaged in accordance with the regulations cited in 13-3.4 shall be transported in accordance with the U.S. Department of Transportation regulations for Class B propellant explosives.

13-3.6 Smokeless propellants shall be stored in shipping containers specified by U.S. Department of Transportation Hazardous Materials Regulations.

13-3.7 Smokeless propellants intended for personal use in quantities not exceeding 20 lb (9.1 kg) shall be permitted to be stored in original containers in residences. Quantities exceeding 20 lb (9.1 kg), but not exceeding 50 lb (22.7 kg), shall be permitted to be stored in residences where kept in a wooden box or cabinet having walls of at least 1 in. (25.4 mm) nominal thickness.

13-3.8 Not more than 50 lb (22.7 kg) of smokeless propellants, in containers of 1 lb (0.45 kg) maximum capacity, shall be displayed in commercial establishments.

13-3.9 Commercial stocks of smokeless propellants shall be stored as follows:

(1) Quantities exceeding 50 lb (22.7 kg), but not exceeding 100 lb (45.4 kg), shall be stored in portable wooden boxes having walls of at least 1 in. (25.4 mm) thickness.

(2) Quantities exceeding 100 lb (45.4 kg), but not exceeding 800 lb (363 kg), shall be stored in nonportable storage cabinets having walls of at least 1 in (25.4 mm) thickness. Not more than 400 lb (181 kg) shall be permitted to be stored in any one cabinet, and cabinets shall be separated by a distance of at least 25 ft (7.63 m) or by a fire partition having a fire resistance of at least 1 hour.

(3) Quantities exceeding 800 lb (363 kg), but not exceeding 5,000 lb (2268 kg), shall be permitted to be stored in a building, provided the following requirements are met:

(a). The warehouse or storage room shall not be accessible to unauthorized personnel.

(b). Smokeless propellant shall be stored in nonportable storage cabinets having wood walls at least 1 in. (25.4 mm) thickness and having shelves with no more than 3 ft. (0.92 m) of separation between shelves.

(c). No more than 400 lb. (181 kg) shall be stored in any one cabinet..

(d). Cabinets shall be located against the walls of the storage room or warehouse with at least 40 ft (12.2 m) between cabinets.

(e). The separation between cabinets shall be permitted to be reduced to 20 ft (6.1 m) where barricades twice the height of the cabinets are attached to the wall, midway between each cabinet. The barricades shall extend at least 10 ft. (3 m) outward, shall be firmly attached to the wall, and shall be constructed of 1/4 in. (6.4 mm) boiler plate, 2 in. (51 mm) thick wood, brick, or concrete block.

(f). Smokeless propellant shall be separated from materials classified by the U.S. Department of Transportation as flammable liquids, flammable solids, and oxidizing materials by a distance of 25 ft. (7.63 m) or by a fire partition having a fire resistance of at least 1 hour.

(g). The building shall be protected by an automatic sprinkler system installed in accordance with NFPA 13, Standard for the Installation of Sprinkler Systems.

(4) Smokeless propellants not stored in accordance with 13.3.9 (1), (2), and (3) shall be stored in a Type 4 magazine constructed and located in accordance with Chapter 8.

Reprinted from NFPA495-85, Standard for the Manufacture, Transportation, Storage and Use of Explosive Materials, © 2001, National Fire Protection Association, Quincy , MA 02269 . This reprinted material is not the complete and official position of the NFPA on the referenced subject, which is represented by the Standard in its entirety.

It basically limits the rights you have to store powder and primers (even loaded ammo would count against it)

Can't find it anywhere. My googlefoo is off
 

kenny

Regular Member
Joined
Apr 11, 2007
Messages
635
Location
Richmond Lynchburg, Virginia, USA
imported post

Generally speaking the Commonwealth does not use any of the NFPA codes except for the National Electric Code.

Explosives and the like fall under the jurisdiction of the local Fire Marshall and/or Building Official.

that is not say they may not refer to the NFPA for guidance.
 